Influence of ambient temperature on current transformers used in power distribution networks.
Resumen:
Most of current transformers (CT) used at power frequency in high voltage networks have little dependence of temperature on errors. Indeed, international standards do not propose any specific accuracy test varying the temperature. However, we have detected that some commercial units of CTs, used in power distribution systems, exhibit large temperature dependence in the range -5 °C to 40 °C. It is proposed to add, to standard CT accuracy tests, an additional one at different temperatures.
2019 | |
Ratio error Phase-shift Accuracy class |
|
Inglés | |
Universidad de la República | |
COLIBRI | |
http://metrologia.org.br/wpsite/aconteceu-em-florianopolis-nos-dias-24-a-2711-o-metrologia-2019/
https://hdl.handle.net/20.500.12008/27857 |
|
Acceso abierto | |
Licencia Creative Commons Atribución - No Comercial - Sin Derivadas (CC - By-NC-ND 4.0) |
Resultados similares
-
On-site calibration of current transformers
Autor(es):: Slomovitz, Daniel
Fecha de publicación:: (2007) -
Electronic system for increasing the accuracy of in-service instrument-current transformers
Autor(es):: Slomovitz, Daniel
Fecha de publicación:: (2002) -
Shielded electronic current transformer
Autor(es):: Slomovitz, Daniel
Fecha de publicación:: (2004) -
Electronic error reduction system for clamp-on probes and measuring current transformers
Autor(es):: Slomovitz, Daniel
Fecha de publicación:: (2000) -
Desarrollo de algoritmos de phase-shifting con pasos arbitrarios
Autor(es):: Ayubi, Gastón A.
Fecha de publicación:: (2020)