Influence of ambient temperature on current transformers used in power distribution networks.

Slomovitz, Daniel - Santos, Alejandro - Trigo, Leonardo

Resumen:

Most of current transformers (CT) used at power frequency in high voltage networks have little dependence of temperature on errors. Indeed, international standards do not propose any specific accuracy test varying the temperature. However, we have detected that some commercial units of CTs, used in power distribution systems, exhibit large temperature dependence in the range -5 °C to 40 °C. It is proposed to add, to standard CT accuracy tests, an additional one at different temperatures.


Detalles Bibliográficos
2019
Ratio error
Phase-shift
Accuracy class
Inglés
Universidad de la República
COLIBRI
http://metrologia.org.br/wpsite/aconteceu-em-florianopolis-nos-dias-24-a-2711-o-metrologia-2019/
https://hdl.handle.net/20.500.12008/27857
Acceso abierto
Licencia Creative Commons Atribución - No Comercial - Sin Derivadas (CC - By-NC-ND 4.0)