Error compensation of current transformers in high voltage networks

Slomovitz, Daniel - Santos, Alejandro

Resumen:

An error compensation technique for measuring current transformers is described. An example is shown for current transformers installed in 150 kV switching devices. Initial ratio errors in the order of 4% and phase shifts around 20 min were reduced to 0.1% and 6 min after the compensation.


Detalles Bibliográficos
2004
Error compensation
Current transformers
Intelligent networks
Energy measurement
Impedance
Saturation magnetization
Circuits
Testing
Magnetic analysis
Inglés
Universidad de la República
COLIBRI
https://hdl.handle.net/20.500.12008/21148
Acceso abierto
Resumen: