A current transformer with nominal ratio 10 A to 10 mA, intended for low-frequency applications, was developed. It includes an electronic device to reduce the magnetizing current, and a continuous shield in the secondary winding (coaxial cable) in order to eliminate the effect of stray capacitances. No guard-source is connected to the shield. It is proposed in this paper to leave the cable-shield-potential floating. This leads to high-accuracy results (ratio errors and phase-displacements in the order of few parts in 10/sup 6/ from 50 Hz to 1 kHz).


Detalles Bibliográficos
2004
Compensation
Current, error
Guard
Measuring transformer
Phase displacement
Power frequency
Shield
Inglés
Universidad de la República
COLIBRI
https://hdl.handle.net/20.500.12008/21146
Acceso abierto
Licencia Creative Commons Atribución – No Comercial – Sin Derivadas (CC - By-NC-ND)
Resumen:
Sumario:A current transformer with nominal ratio 10 A to 10 mA, intended for low-frequency applications, was developed. It includes an electronic device to reduce the magnetizing current, and a continuous shield in the secondary winding (coaxial cable) in order to eliminate the effect of stray capacitances. No guard-source is connected to the shield. It is proposed in this paper to leave the cable-shield-potential floating. This leads to high-accuracy results (ratio errors and phase-displacements in the order of few parts in 10/sup 6/ from 50 Hz to 1 kHz).